Please find below magnetic induction values at 1 meter. These values are simulated from a model, created and adjusted on some real measures.

Range & rating    Magnetic induction value at 1m (µT)
KSA100    0,23
KSA160    0,39
KSA250    0,64
KSA400    0,99
KSA500    0,66
KSA630    0,82
KSA800    1,04
KSA1000    1,20
KTA800    0,31
KTA1000    0,46
KTA1250    0,63
KTA1600    0,90
KTA2000    1,23
KTA2500    1,63
KTA3200    2,06
KTA4000    2,98
KTC1000    1,11
KTC1350    1,40
KTC1600    1,54
KTC2000    0,39
KTC2500    0,58
KTC3200    0,80
KTC4000    1,13