How to set the Dip Switch - B i the UA Controller, Source Change Over System.

FA332220

29 September 2021

Switch B: used to select action of the UA Controller in the event of a generator fault
Switch B = 1: No action. The priority load remains connected to the "Normal" source.
Switch B = 0: The "Normal" source is opened. The load is isolated from the "Normal" source (no power supplied).
;