With a UA cintroller is it possible to start the Generator of the ATS system only without Switching to the Reserve Supply?

FA315858

15 April 2021

The contacts 29 - 31 (Startup Order) of the UA controller should be externally connected with a switch to give an external signal to start the Generator. There is no internal connection or program to acheive this in UA controller.