FA285498
28 July 2022
Issue:Cannot change Forced Local parameter from NO
Product line:ATV61, ATV71, Altivar 61, Altivar 71
Environment:All
Cause:Customer wants to use Forced Local but the drive will not allow the change.
Resolution:Forced local is not compatible with the Profile set to IO. To use the Forced Local function, the Profile needs to be set to Separate or Not Separate.