FA277042
28 September 2021
Issue: What is 2 wire type on the Altivar 61/71?
Product Line:Altivar 61, Altivar 71, Altivar 312, Altivar 320, Altivar 630, Altivar 930
Environment:All serial numbers
Cause:N/A
Resolution:2 wire type will determine how the drive responds to the run command when the VFD is powered with the run command active, while in 2 wire control : See examples below
[2 wire type] [Transition] (trn)LEL [Level] (LEL): State 0 or 1 is taken into account for run (1) or stop (0). The unit will run if run command is active on power up and the VFD is in 2 wire control
trn [Transition] (trn): A change of state (transition or edge) is necessary to initiate operation, in order to prevent accidental restarts after a break in the power supply. The run must transition from low to high on power up. PFO [Fwd priority] (PFO): State 0 or 1 is taken into account for run or stop, but the “forward” input always takes
priority over the “reverse” input.