FA277035
05 June 2022
Issue: Ramp increment meaning for the Altivar 61/71.
Product Line:Altivar 61, Altivar 71
Environment:All serial numbers
Cause:N/A
Resolution:Ramp increment is a parameter that will change the resolution of the listed parameters: see below
Inr M
[Ramp increment] 0.01 - 0.1 - 1 0.1
0.01
[0.01]: Ramp up to 99.99 seconds
0.1
[0.1]: Ramp up to 999.9 seconds
1
[1]: Ramp up to 9,000 seconds
This parameter is valid for [Acceleration] (ACC), [Deceleration] (dEC), [Acceleration 2] (AC2) and [Deceleration 2]
(dE2).