What can cause the ATV61 or ATV71 drive to fail the auto diagnostics transistor test showing ok, open, ok, open on all of the transistors in the test?
FA248982
28 September 2021
Issue:ATV61 or ATV71 possible causes for a fail in the auto diagnostics transistor test showing ok.
Product Line:
Altivar ATV61 and ATV71
Environment:
All
Cause:
They run the Auto diagnostics test and the drive fails showing ok open ok open on all of the tested IGBTs.
Resolution:
The motor may not be connected to the drive when you start the test. Make sure the motor is connected to the motor with no disconnect between the motor and drive before starting the test.