Frequently asked questions
What is the heat loss for the ATS22C32S6U?
FA245246
28 July 2022
Issue:Needs the heat loss for the ATS22C32S6U
Product Line:
ATS22
Environment:
ATS22C32
Cause:
N/A
Resolution:
Heat loss :
During starting @ 3.5 ICL (Nominal current of the softstart) : 3699 Watts
During Steady State at full load : 96 Watts
Electronics : 20 Watts
Shorting Contactors : 14 Watts
Fans : 20 Watts
---------------------------------------------
Total at Steady State : 150 Watts