FA243521
14 June 2022
Issue:Start an ATV312 using Modbus
Product Line:Variable Frequency Drives
Environment:Applies to ATV312
Cause:Customer is not able to start the drive using Modbus.
Resolution:Suggested to follow the status chart and send the values to the command word in sequence Hex 6 then 7 then F to Address 8501 (assuming there is no offset)