FA243516
28 September 2021
Issue:Com scanner address input/output tables on ATV630
Product Line:Altivar Process drive.
Environment:All models, All serial numbers.
Cause:Information not available in current literature.
Resolution:Com scan IN value 1: 12741 dec
Com scan IN value 8: 12748 dec
Com scan OUT value 1: 12761 dec
Com scan OUT value 8: 12768 dec