Issue:Can I see the status of the analog / logic inputs of the ATV61/71 series drives on the keypad?
Product Line:Altivar Machines, Altivar 61, Altivar 71
Environment:All models, All serial numbers, VW3A1101 equipped
Cause:Customer needs to display this information for troubleshooting / installation purposes.
Resolution:From the main menu, select Drive menu (menu 1) then Monitoring menu (Menu 1.2) Under Monitoring menu, select I/O map. From here, to display the incoming voltage/current to the analog inputs, select Analog Inputs Image. To display the status of the logic inputs, select Logic Input Map.