What is the maximum rated AC current at AC voltage for the auxiliary contacts of C60.

FA22617

30 September 2021

The maximum rated AC Voltage and AC Current for the Category AC12 (IEC 60947-5) auxiliary contacts OF, SD, OF+SD/OF, OF.S (Reference - 26924, 26927, 26929, 26923) of C60 MCB is as below:
 
 
AC Voltage
AC Current
380…415V
3 A
220…240V
6 A
 
 
The maximum rated AC Voltage and AC Current for the Category AC15 (IEC 60947-5) auxiliary contacts OF special (Reference - 16940) of C60 MCB is as below:
 
AC Voltage
AC Current
220…240V
6 A