FA22610
30 September 2021
The contact resistance per pole for C60 range of MCBs is as tabulated below:
C60 Test for In at 50 Hz, Value per pole
Rated Current (A) | Impedance (milliohm) |
0.5 | 8800 |
0.75 | 5267 |
1 | 2300 |
1.2 | 1667 |
1.5 | 933 |
2 | 638 |
3 | 248 |
4 | 150 |
5 | 100 |
6 | 75 |
7 | 57.14 |
8 | 43.25 |
10 | 17 |
13 | 11 |
15 | 10 |
16 | 10.13 |
20 | 7.35 |
25 | 4.88 |
30 | 3.47 |
32 | 3.47 |
35 | 2.57 |
40 | 2.88 |
50 | 1.9 |
60 | 1.5 |
63 | 1.52 |
Note: The resistance is equivalent to the impedance as the inductance between the contacts is negligible.