Why does the display light of Micrologic 6.2 trip unit of Compact NSX not glow even when the load reading is displayed.

FA22584

30 September 2021

Unlike other range of Micrologic the backlighting or display light of Micrologic 6.2 is not self powered by the primary current.
 
A separate external 24VDC power supply is required for the working of the backlight of Micrologic 6.2. For this, 24VDC power supply connector (LV434210) has to be used.