Why does the motor run forward in bypass but reverse in AFC?

FA176580

28 September 2021

Issue:
Motor runs wrong direction in AFC

Product Line:
ATV212, SFLEX

Environment:
All models

Cause:
None

Resolution:
Recommendation , swap two of the drive output leads T1-T2-T3 (motor leads). Swap the leads between the drive output terminals (load side) and drive output contactor (line side).

;