Yes, it is possible to install the rectangular sensor at the incoming side of the Masterpact Air circuit breaker (ACB).
The earth leakage protection in Micrologic 7.0 trip unit will work correctly irrespective of whether the rectangular sensor is installed in the upstream or downstream.