FLC1 is the parameter to enter the Motor nominal current in TeSys T. In this parameter, the Motor nominal current is entered as a percentage of the rated value of the TeSys T.
Example:
For TeSys T of range 8Amps (LTMR08) and a motor of 2 Amps nominal current, you have to set the FLC1 value to 25% because the Motor nominal current is 25% of the full load current of TeSys T Module (LTMR08).
This means that the current in register 466 (value of current in percent) take the value of 100% when you reach 25% of the current of the TeSys T Module rated current value.