FA12078
30 September 2021
Yes, Reflex Tripping is available in all Compact NS/NSX Switch Disconnectors.
The threshold of the Reflex Tripping auto-protection is about 20xIn and time delay is less than 10 ms, as shown in the attached tripping curves.
The Reflex Tripping is due to "Piston - which is purely mechanical” and not due to the trip unit.
Thus the Reflex Tripping being a mechanical controlled function is also available in the Compact NS/NSX Switch Disconnectors.