Quantcast

Digital input status changes are not reflected in Sequence of Events Recorder (SER) 7

FA212454

23/07/2020

Issue
When the status of a CM3/CM4 digital input changes, the change is not shown in SER. In addition, no errors are present in SER.

Product Line
SER 7.x

Cause
The Circuit Monitor's input is incorrectly configured


Resolution
Set the CM's digital input Mode to SER
Enable the CM's onboard SER Data Log with a non-zero record count.