What is the pulse width on digital output for a 6200 meter?

FA211914

24/01/2018

Issue:

Pulse width output
 
Product Line:

 ION6200
 
Environment:
 ION 6200
 
Cause:
Time Constant, kT, is the number of units (kWh,kVah,kVARh) per output transition.
 
Resolution:
 The digital output uses KY pulsing. This means that the relay changes from open to closed or from closed to open whenever kT units have been measured (20 transitions/second maximum).