Issue In firmware versions prior to 1.005 RS and 1.012 OS, there were known issues with the way the BCPM processed data in 2 pole and 3 pole configurations. Product Line Branch Circuit Power Meter (BCPM) DLF-3000 Environment Firmware Upgrade Cause Old firmware Resolution Firmware was released on January 18, 2011 to address an issue with the way BCPM processed data in 2 pole and 3 pole configuration. The versions released are 1.005 RS and 1.012 OS. DLF-3000 is used to send the firmware to the meter. The following link is to the latest firmware for a BCPM: Branch Circuit Power Meter (BCPM). Use the following link to download the DLF-3000 software: DLF-3000 Download *Reference FA212885 for an example of how to upgrade BCPM firmware.