What are the control power requirements for the Enercept Network Adapter (ENA)?

FA203658

24/01/2018

Issue
What are the control power requirements for the ENA?

Product Line
Enercept Meter, ENA

Cause
User would like to know control power range for ENA

Environment
Installing ENA

Resolution 
The control power requirements for the ENA (Enercept Network Adapter) are as follows: 9-30Vdc or 12-24Vac ; not including power factor, 1.5W max, 125mA max @12Vdc, 65mA max @24Vdc.