MASTER YOUR CASTLE with your new build or reno project
Enter competition

Can one place any I/O module in any position in an IOX (side car) module?

FA203267

24/01/2018

Product Range
CM4000 Series

Environment
I/O Module

Resolution
One can place Digital Inputs and Relay Outputs in any pattern. However, Analog Inputs and Outputs must NOT be placed in consecutive slots. In other words, there must always be a slot between any two Analog modules. This slot can contain a Digital module, but no Analog module.