Are Harmonics Included in the CM2 KVAR Demand?

FA202893

3/08/2018


Product Line
CM2000

Environment
Harmonic reading

Resolution
The KVAR demand defaults to the "fundamental only" value ignoring harmonic data. To include harmonic data, write command 2331 to register 7700.

See FA211912 for how to write registers from the front display of the CM2000.