Which IODDT data type would I use for an M340 analog input module that includes the input value and other channel information?

FA199148

28/11/2018

The IODDT for all channel properties is T_ANA_IN_BMX..
This Data Type will yield all of the channel's properties and diagnostic information.

If you only want the channel VALUE and CH_ERROR properties you can use theT_ANA_IN_GEN  Data Type.
.

Legacy KB System (APS) Data: RESL212293 V1.0, Originally authored by DaSo on 08/12/2013, Last Edited by DaSo on 08/12/2013