Why is the 140CPS12420 not compatible with the 140CPS12400 when used in a redundant configuration ?

FA198934

31/10/2018

The two power supplies cannot share the output current  due to the difference in their internal design. The power supplies use different APS_SENSORS which do not have the same gains.
 

Legacy KB System (APS) Data: RESL210789 V1.0, Originally authored by DaSo on 02/27/2013, Last Edited by DaSo on 02/27/2013
Related ranges: Modicon Quantum