What is the time-out value for the Advantys STB Ethernet NIM STBNIP2212 to go into a fallback state when communication to the Master is lost?

FA197454

31/05/2019

The time-out value is referred to as the Holdup Time. It is configured via the embedded web pages. Select the menu Configuration -> Master Controller. The value entered is in milliseconds ranging from 300ms-120000ms. A value of 0 is indefinite holdup time. Holdup time parameters are stored in Non-Volatile RAM.