What is the procedure for removing an ADVC controller from service for testings without tripping the recloser?

FA180179

24/01/2018

For unit removal without tripping the recloser: disable the trip and close switches located on the ADVC controller unit, power down DC, power down AC then disconnect the switchgear
Applying power for testing: power up AC, power up DC and test
Unit re-installation: connect switchgear, power up AC, power up DC, enable the trip and close switches