Is it possible to remove the ADVC controller without tripping the recloser?

FA180178

24/01/2018

The ADVC controller was designed to be removed from service without tripping the recloser. To disable the trip upon removal, use the two switches located in the ADVC enclosure labeled Trip and Close then set them to disabled before removal.