How to time synchronize PM800 or Sepam series device with PowerLogic SCADA?

FA179966

27/04/2015

You can manually do it following the procedure as per below.

a. You must login with operator2, engineer, administrator or kernel user level.

b. Click on a device à List à Resets as per below.

c. Click on Activate from Device Date/Time as per below.

d. Click on OK

 

Please check also Updated information with our Powerlogic L3 Team

AEDL3


Original Author: YJ

Public

All content © 1992-2009 Schneider Electric


Legacy KB System (APS) Data: RESL200959 V1.0, Originally authored by KBAdPM on 01/08/2010, Last Edited by KBAdPM on 01/08/2010
Related ranges: Sepam series 80, Sepam series 40, Sepam series 20, PM800 series, PowerLogic SCADA 7.1