Does the green LED need to be ON in order to communicate to the MSA141 or MET148-2 remote modules for the Sepam Series 20, 40,60 and 80 relay?

FA179948

11/07/2020

Issue    
Whe installing the MET148-2 the green LED is not on.

Product Line
MSA141
MET148-2

Resolution
The active green LED must be on in order to communicate to the MSA141 or MET148-2 remote modules. The active green LED means that the module is powered and receiving control power from the Sepam relay. If the green LED is OFF, verify that the CCA77x cable is wired correctly from the "D" port of the Sepam to the "Da" port of the remote module. Also, verify that the Sepam relay is energized, or else the remote module will not receive the power from the Sepam relay.