Are logical equations lost in the Sepam Series 40 , 60 or 80 relay after reloading factory settings using SFT2841?

FA179946

13/05/2020

Issue       
Does my equations in equation editor get deleted if Sepam is set to Factory settings?

Product Line     
Sepam 40 Series
Sepam 60 Series
Sepam 80 Series

Resolution
When reloading factory settings using SFT2841, all parameter settings will be erased except for logical equations.

If removing these equations is necessary, they must be removed manually using the SFT2841 commissioning software.