Invalid reply error message on RSLogix when configuring an ATV61 or ATV71 with ethernet IP card.

FA175313

24/01/2018

Issue:
Invalid reply error on  RSLogix configuring an ATV61 or ATV71 with ethernet IP card.

Product Line:
Altivar ATV61 and ATV71

Environment:
VW3A3316 ethernet IP card on the ATV61 or ATV71 drives

Cause:
RSLogix is configured for double integer

Resolution:
Set up RSLogix configuration for single integer.
Using assemblies 100 and 101.