Why will the analog output not change when the AO1 assignment is set to Torque 4Q?

FA174665

17/07/2020

Issue:
No change on analog input when AO1 assignment is set to Torque 4Q.
 
Product Line:
Altivar 71
 
Environment:
All part numbers all versions
 
Cause:
The motor control type is set to either V/F 2pts or V/F 5pts
 
Resolution:
The Motor control type must be set to something other than V/F 2pts or V/F 5pts for this function to work.   Once the Motor Control type has been changed the analog output should begin to respond to changes in the motor torque.