Can the PID feedback signal be replicated to another drive?

FA173577

11/08/2020

Issue:
Customer wants the analog signal to operate two drives from one source.

Product line:
Altivar Machines, Altivar 61, E-Flex

Environment:
All models, all serial numbers 

Cause:
One PID signal to operate two drives. 

Resolution:
Under Drive Menu > Inputs/Outputs Configuration > AO1 Configuration > AO1 assignment, change this parameter to PID feedback.  Use the AO1 and COM terminals to feed the reference signal into the next drive.