What indicates that he bypass contactor has closed on the ATS22 soft starter?

FA173024

24/01/2018

Issue:
What indicates that he bypass contactor has closed on the ATS22 soft starter?

Product line:  
Altistart 22

Environment:
All models, all serial numbers

Cause:
The bypass contactor is internal and cannot visually see it is closed.

Resolution:
Assign one of the relays to "run".   Relay is energized when the bypass contactor is closed.  The continuity can be checked across this relay to verify the bypass contactor has closed.