MASTER YOUR CASTLE with your new build or reno project
Enter competition

Uniflair PCO1 Cool Setpoint Reverts to 0

FA170977

6/03/2018

Issue:
Uniflair PCO1 Cool Setpoint Reverts to 0

Product line:
Uniflair

Environment:

Cause:
Cool Setpoint revert to 0

Resolution:
If the cool setpoint reverts to 0 or another value after setting it through the front screen, remove all communication (web, modbus, ect) connections. These have the ability to change the setpoints and can cause it to revert to a different setpoint if not set up properly.