Quantcast

How is the ATV12 programmed to run via logic input on LI1 and adjust speed via dial?

FA168125

20/06/2020

Issue:   
How is the ATV12 programmed to run via logic input on LI1 and adjust speed via dial?
 
Product Line:   
ATV12
 
Environment:  
All
 
Cause:  
Terminal command with local reference
 
Resolution:   
Wire the run contact to +24 - LI1.
In the CtL menu, set Fr1 = AIV1, CHCF = SEP and Cd1 = tEr.
Press the dial twice to adjust speed as a percentage of the range LSP - HSP.