MASTER YOUR CASTLE with your new build or reno project
Enter competition

InRow: What is capacity regulation?

FA166974

29/04/2019

Issue:
What is capacity regulation?

Product line: 
ACRD100, ACSC100

Environment:
All versions and serial numbers.

Cause:
Configuration & Installation

Resolution:
Capacity regulation is achieved by using an electronic Hot Gas Bypass Valve (HGBV) which allows the unit to operate at low load conditions down to 2.5KW without compressor recycling. As the suction pressure drops the valve will start to feed discharge gas into the evaporator coil raising the overall suction pressure.  The HGBP valve is also used to equalize system pressures at start-up and will also open in the event a high head pressure event may occur.