What ATV31 parameter needs to be changed when a dynamic braking resistor to PA and PB?

FA130812

3/08/2020

Issue:   
N/A
 
Product Line: 
ATV31
 
Environment:  
All
 
Cause:  
Parameters for braking resistor application
 
Resolution:   
FUN menu then rPC sub-menu then brA turn if off.