Can you use a GFI (Ground fault interrupt) on a 115V single phase input with a ATV11 drive?

FA129933

21/07/2020

Issue:   
Using  GFI (Ground fault interrupt) on a ATV11.
 
Product Line:   
ATV11
 
Environment:  
All
 
Cause:  
Feeding the ATV11 with GFI
 
Resolution:   
The PWM in the drive can cause problems with the GFI, because of the capacitance to ground. It is not recommend to use a GFI with the drive.
If a GFI have to be used, then suggest installing an isolation transformer between the GFI and the drive. Also the motor needs to be properly grounded.