FA129611

21/08/2018

Issue:
GV2 Aux contacts versus Fault contacts 

Product Line: 
Contactors and Starters - IEC 

Environment:
Tesys GV Manual Starter

Resolution:
The instantaneous aux contacts change state to follow the GV2 control as it is mechanically moved to the energized or deenergized position. The fault signaling contacts change state in the event of any fault (i.e. overload or short circuit) condition only. Otherwise, they are not affected by the movement of the control from energized to deenergized state.