A DC shunt trip on a Powerpact M, P, or R frame breaker fails to trip the breaker with rated voltage applied.

FA121336

31/05/2018

Product Line:
Circuit Breakers
PowerPact M, P, and R

Environment:
Electrical Distribution Equipment

Resolution:
Polarity needs to be - on C1 and + on C2. If this does not correct the problem with proper voltage applied, replace the shunt trip.