What is the minimum distance required for cable interlocking between two Masterpact ACB’s.

FA12106

11/07/2012

Masterpact Air circuit Breaker (ACB) could be placed just side by side, there is no safety clearance required for cable interlocking between two Masterpact ACB’s.

Though you have to ensure that the radius of 100 mm should be maintained for the curvature of the cable.