Will a 6.0A trip unit be backlit when it has current enough to power the trip unit?

FA114244

13/03/2019

Product Line:
Circuit Breakers
PowerPact P and R
Masterpact NW and NT
Micrologic Ammeter

Environment:
Electrical Distribution Equipment

Resolution:
Yes, all A type trip units should be lit when the breaker has enough current to power the trip unit. 

NOTE:  An alternative option would be to apply 24vdc to F1/F2 terminals of the trip which will power the trip unit all the time.

See trip unit bulletin for more information 48049-136-05