With an Econoflex drive, why is it not possible to get the drive to Autotune?

FA106202

20/12/2016

It is possible to autotune this drive. If this unit has bypass, the isolation contactor must be closed to provide a good connection between the drive and the motor.

Also, there must not be a fast stop or freewheel stop active.

Make sure that any logic input programmed as Fast Stop or Free Wheel stop is on (high or with +24 VDC present), but all other logic inputs have to be off (low).