Why does ATS48 not operate when wired like the recommended diagram on page 74 of the June 2002 manual?

FA104734

24/01/2018

The user's manual recommended diagram on page 74 is incorrect for proper operation.  
On line 2 of the ladder diagram after fault relay R1A to R1C connection the coil that is labeled TR for trip relay should be a FR coil for fault relay.
Then should add a line after this that has a NC (normally closed ) FR ( fault relay ) contact in series with a TR ( trip relay ) coil.

This configuration would then allow proper operation of unit.