    Multi-9 C60 Breakers: Values for Watts Loss and Voltage Drop per pole

    Issue:
    Power Loss
    Watts Loss
    Contact Resistance
    Voltage Drop

    Product Line:
    Circuit Breakers

    Environment:
    Applies to Multi-9, C60 Circuit Breakers (UL489 and UL1077)

    Resolution:
    The attached document gives the Power Loss (Watts Loss) and Voltage Drop per pole, at rated current of the breaker (nominal current). For example, a 1A breaker would be expected to have a Watts Loss per pole of 2.3 W, at rated current of 1A. This information can be used to calculate voltage drop when used at other than nominal current.