    How can an ATS46 or ATS48 be used with an undersized motor or no motor?

    Issue:
    How can an ATS46 or ATS48 be used with an undersized motor or no motor?

    Product Line:
    ATS46, ATS48

    Environment:
    All

    Cause:
    NA

    Resolution:
    A minimum load current is required for SCR conduction. Starter will trip on PHF (Phase Fault) if the motor current draw is less than 10% of the nominal motor current (adjustable down to 5% on ATS48).

    A very small motor or motor loads that can not pull adequate current may require a smaller soft starter.
    For testing purposes only, the SST parameter can be turned on under Level 3 parameters(drC menu on ATS48). This SST mode will automatically reset to "NO" when power is cycled.
    SST will NOT allow the soft starter to operate with no motor.