    What causes the Precharge Capacitor Fault on Altivar Process drives?

     Issue:
    What causes the Precharge Capacitor Fault on Altivar Process drives?

    Product line:
    Altivar Process, ATV600, ATV900

    Environment:
    all

    Cause:
    Unstable mains voltage
    DC link capacitors lifetime exceeded

    Resolution:

    After switching on the DC Bus is charged by the rectifier brigde, if the DC bus is not stabilized within 5s (for 400ms +/- 5V at 400-480V OR +/- 8V at 690V) the fault CrF occours.
    The detection of the CrF fault is activated when VBUS voltage > USFH.


    Power cycle the drive, make sure the display goes completely dead before turning back on
    Measure the Mains Voltage coming into the drive and compare with the voltages shown in the Display menu
    Check the internal wiring from the mains input up to the rectifier / AFE brick
    Check the grounding